PUE explained: How we achieve a value of 1.14

June 17, 20267 min read
Hero-PUE-Hetzner-Blog.webp
Back to Overview
What does PUE mean, and what does it measure?
How is PUE measured?
How does Hetzner keep PUE so low?
Free air cooling: The biggest driver of a low PUE
UPS with 99% efficiency: Minimal losses in power distribution
Efficient building structure: Less infrastructure, better PUE
92% utilization: Why high load improves PUE
Conclusion: Efficiency is a matter of consistency

In this article

  • What does PUE mean, and what does it measure?
  • How is PUE measured?
  • How does Hetzner keep PUE so low?
  • Free air cooling: The biggest driver of a low PUE
  • UPS with 99% efficiency: Minimal losses in power distribution
  • Efficient building structure: Less infrastructure, better PUE
  • 92% utilization: Why high load improves PUE
  • Conclusion: Efficiency is a matter of consistency

In this article

  • What does PUE mean, and what does it measure?
  • How is PUE measured?
  • How does Hetzner keep PUE so low?
  • Free air cooling: The biggest driver of a low PUE
  • UPS with 99% efficiency: Minimal losses in power distribution
  • Efficient building structure: Less infrastructure, better PUE
  • 92% utilization: Why high load improves PUE
  • Conclusion: Efficiency is a matter of consistency
TL;DR
PUE, short for “Power Usage Effectiveness”, shows how much electricity reaches the IT systems and how much the supporting infrastructure uses, for example for cooling and power distribution. The more energy flows directly into IT, the more efficiently the data center operates. With an average PUE value of 1.14, we achieve an exceptionally low figure. We do this through free cooling with outside air, modern UPS technology, short power paths, minimalist building structures, and an extremely high IT utilization rate of 92%. In practical terms, only about 12% of the electricity goes into the surrounding infrastructure, while 88% flows directly into IT.

Without electricity, nothing runs in a data center: from the servers to the building’s technical infrastructure. From an environmental perspective, it is important to know where the electricity comes from and where we can save it. We source 100% of the electricity for our German and Finnish data centers from renewable energy. That leaves the question of where further savings are possible. A data center’s PUE value provides one answer.

In this article, we take a closer look at how this value is calculated and what it actually means.

What does PUE mean, and what does it measure?

PUE stands for “Power Usage Effectiveness” and describes how efficiently a data center uses energy. The value shows how much energy a data center needs in total for one kilowatt hour to reach the IT systems. The formula behind it is refreshingly simple:

Content-PEU-Calculation-1-en-Hetzner-Blog.svg

The perfect value would be 1.0. In that case, every kilowatt hour would flow directly into IT, with no additional energy needed for operations. In practice, however, that is impossible. Air conditioning units, UPS systems, transformers, power distribution, and lighting also need energy; and losses inevitably occur during operation.

We call the portion that does not reach IT “overhead”. The smaller the overhead, the closer the data center gets to the perfect 1.0, and the better the PUE.

What does this mean in concrete terms for us? Our data center park in Nuremberg used around 55 GWh of electricity in 2024. With a PUE of 1.14, this means that for every kilowatt hour flowing into IT, the rest of the infrastructure needs only 0.14 kilowatt hours. In other words, around 88% of the electricity goes directly into the servers. This can be easily calculated by dividing 1.00 by 1.14.

For comparison, the German industry average was 1.46 in 2024. With the same IT load, a data center like that uses around 28% more electricity than one with a PUE of 1.14. Over a full year, this difference adds up to very large amounts of energy.

One important note: PUE says nothing about how efficiently the IT itself operates, even though IT consumes the largest share.

Fun fact: Back in 2011, TÜV SÜD measured a PUE of 1.1242 for our park in Falkenstein. According to TÜV SÜD, this was the lowest value it had measured up to that point. The industry average at the time was still around 1.8. (Source: TÜV SÜD)

Content-PEU-Usage-Comparison-Hetzner-Blog_1.webp

How is PUE measured?

To make the PUE value truly comparable, we need to measure power consumption precisely. We cannot treat it as a snapshot. One cool week would distort the picture. That is why we measure over a longer period, ideally a full year, so that all four seasons and their different temperatures are included.

For this, we measure consumption in strictly separate categories:

  • IT consumption: servers, storage, network
  • Building/infrastructure consumption: cooling, power distribution, lighting, security

We measure in accordance with a specific standard, DIN EN 50600-4-2. It defines how providers should measure and calculate these values so they can compare them objectively. This also allows us to meet the requirements of the German Energy Efficiency Act (EnEfG).

How does Hetzner keep PUE so low?

First of all, we do not achieve this low value by making one single, especially effective decision. It results from a combination of many technical measures and an extremely efficient infrastructure, from the building itself to all supporting systems.

The key to a low PUE value lies in making non-IT infrastructure as energy-efficient as possible and avoiding unnecessary losses.

We can divide these areas roughly into three groups:

  • Cooling
  • UPS (uninterruptible power supply) and power distribution
  • Other building functions: lighting, security systems, access systems, monitoring, administration

When IT consumption increases while everything else stays the same, PUE decreases. The smaller the gap between IT consumption and total consumption, the better.

Free air cooling: The biggest driver of a low PUE

Our cooling concept is where we perform particularly well. Instead of energy-intensive cooling technology, we use the most economical cooling medium available: outside air.

This is how it works: The data center draws in cool outside air through air shafts on the facade, guides it through cold aisles and raised floors directly to the servers, and keeps warm and cold air strictly separated. The heated air then leaves the building again. Apart from a few fans, this requires very little electricity.

We do not simply send all of the warm exhaust air outside. We use part of it to heat office spaces, which saves additional energy.

We do not use water-based cooling, such as dry coolers or evaporative coolers at all. This saves water and also eliminates several power-hungry components that account for a large share of overhead in other data centers.

On particularly warm days, air conditioning units can switch on as a supplement. Depending on the location, year, and climate conditions, however, they only run on a few days per year. As a result, their share of power demand is usually around 3 to 7 percent, and no more than about 10 percent of the total facility energy. This is one of the main reasons for our extremely low PUE.

Content-PUE-airflow-Hetzner-Blog.webp

UPS with 99% efficiency: Minimal losses in power distribution

For the power supply, we rely on very short cable routes and modern UPS systems with a high efficiency of up to 99%. This is also a top-tier value compared with the industry average. We therefore keep electrical losses as low as possible.

The fewer transformers and conversion stages there are, the less energy is lost along the way. Thanks to the compact, modular design of our data centers and our high rack density, we need less infrastructure per kilowatt of IT power. This further increases efficiency.

By avoiding water-based cooling systems, we operate fewer overhead devices, which also has an indirect and positive effect on our UPS’s efficiency.

Efficient building structure: Less infrastructure, better PUE

This category shows the intelligent planning we put into our data centers. We consistently design our buildings to maximize efficiency, starting with the architecture. Our design focuses on what is technically necessary and leaves out any superfluous, energy-intensive systems. The building structure itself also helps minimize energy losses and simplify operations.

This allows us to avoid lighting large unused areas, operating complex ventilation or air conditioning systems for ancillary rooms, and maintaining unnecessary technical infrastructure. Lighting is active only where we need it. We have minimized the energy footprint for our buildings’ security, access control, and monitoring systems.

We install all technical systems in a way that makes maintenance, repairs, and later replacement straightforward.

92% utilization: Why high load improves PUE

One final, often underestimated factor is utilization. Across all locations in Germany and Finland, our average utilization is around 92%, an exceptionally high value. This has a direct positive effect on PUE. Why? The formula is:

Content-PEU-Calculation-2-en-Hetzner-Blog.svg

If IT consumption were lower, the remaining infrastructure components, such as lighting or security technology, would still have to keep running. In relation to the IT load, the infrastructure share would then be significantly larger, and the PUE would rise.

High utilization therefore ensures that the existing infrastructure is used optimally and that the PUE value decreases. In other words, a well-filled hall operates more efficiently than one that is half empty.

Conclusion: Efficiency is a matter of consistency

We show that well-planned architecture, smart cooling, and a clear technical approach can achieve enormous savings. The PUE of 1.14 is the result of a system designed correctly from the ground up.

At the same time, we continue working toward an even more efficient future. New technologies, optimized cooling, and a consistently streamlined building layout will continue to increase efficiency in the coming years.

Company
Content-profile-Macrea-Adrian-Hetzner-Blog.webp

Adrian Macrea

Editor

Share article

Related articles

Hero-Story-of-Hetzner-Hetzner-Blog.webp
Our story: From Gunzenhausen to the world
June 17, 20269 min read
Hero-Nachhaltigkeit-Hetzner-Blog.webp
EMAS, PUE: How we put sustainability into practice
June 17, 20267 min read
Hero-3D-Print-Hetzner-Blog.webp
3D printing: How we print our own server parts
June 9, 20266 min read
Logo
Subscribe to our newsletter

Subscribe to our newsletter

Hetzner
  • Company
  • Our Customers
  • Sustainability
  • new
    Blog
  • Career
  • Pressroom
Support
  • Support Center
  • Contact
  • Downloads
  • Hetzner Docs
  • Status
Legal
  • Legal notice
  • Data privacy
  • System policies
  • Terms and conditions
  • Digital Services Act
  • Abuse form

©2026 Hetzner Online GmbH. All Rights Reserved. Prices